          The quality of survival, technology and development
          Quality for survival, technology for development
          YB-12/0.4 type High-Voltage/Low-Voltage Prefabricated Substation
          YB-12/0.4 type High-Voltage/Low-Voltage Prefabricated Substation
          YB-£12/0.4 type High-Voltage/Low-Voltage Prefabricated Substation

          Description:

          YB-£12/0.4 type High-Voltage/Low-Voltage Prefabricated Substation can realize ring main type and terminal type power supply mode. It’s applicable to urban public power distribution, street lamp electricity, industrial and mining enterprises, etc.. In addition, it meets the Standards GB/T17467 and IEC601330.

          Structure features:

          u Small size, light weight, beautiful appearance and environmental coordination.

          u Composed of a high pressure chamber, a transformer chamber and a low pressure chamber.

          u Terminal, ring or dual power supply.

          u Single or dual transformer power supply solution.

          u Oil-immersed power and Dry power transformer.

          u Sufficient natural vents and insulation measures (forced cooling if need).

          u Multiple materials or a combination of both help long-term use outdoor.

          u Small size when using SF6 load switch cabinet, and suitable for community construction, street lighting engineering renovation.

          u Reliable detection of short-circuit and single-phase ground faults because of RTU in the high-voltage ring main cabinet.

          u Complete and reliable Five-protection system. Easy to operate and maintain.

          Using environment:

          u Temperature: Min -45℃~Max+40℃;

          u Relative humidity: Daily average ≦95%; Monthly average≦90%;

          u Altitude: ≦1000m;

          u Shock level: Horizontal acceleration 0.4m/s2,Vertical acceleration 0.15m/s2;

          u Installation location: The place with no severe impact, serious pollution and chemical corrosion, no conductive dust and explosion risk.

          When the conditions of use exceed the above range, the user shall negotiate with us to determine the allowable range or take corresponding supplementary technical measures.

          Item

          Unit

          Value

          High-Voltage unit

          Rated frequency

          HZ

          50

          Rated voltage

          KV

          10

          Maximum working voltage

          KV

          11.5

          Rated current

          A

          400、630

          Take-over current

          A

          870

          Power frequency withstand voltage (Phase to phase, Phase to ground/Isolation fracture)

          KV

          42/48

          Lightning impulse withstand voltage(Phase to phase, Phase to ground/Isolation fracture)

          KV

          75/85

          Rated short-circuit breaking currentCurrent limiting fuse

          KA

          31.5

          Transformer unit

          Rated voltage

          KV

          6、10

          Rated Capacity

          KV/A

          10-1250

          Tap range

          %

          ±2*2.5%、±5%

          Connection group

           

          Yyn0、Dyn11

          Impedance voltage

          %

          4、4.5、6、8

          Low-Voltage unit

          Rated voltage

          V

          220、380、690、800

          Main circuit rated current

          A

          50-4000

          Branch current

          A

          5-800

          Shell

          IP gradeConventional product

           

          High-Voltage Room IP33; Transformer Room IP23; Low-Voltage Room IP33

          Noise level

          dB

          50

          Technical Parameters: